The safety and structural integrity of anaerobic digesters rely entirely on the precise management of internal pressures. For decades, the specification of digester gas safety equipment has largely been a choice between two established North American suppliers. Engineers evaluating Varec Biogas (Ovivo) vs Shand & Jurs for Digestion applications are navigating a landscape defined by legacy installations, subtle differences in sealing technology, and critical reliability requirements. Both are genuine specialists in this equipment class — which makes this one of the few head-to-head comparisons in digestion where the two companies actually compete for the same scope. The nuances in their pressure/vacuum relief valve (PVRV) designs, flame arrester technologies, and waste gas burner configurations lead to real differences in operating expenditure and site safety profiles.
Digester covers—whether floating, fixed, or membrane—operate within extremely narrow pressure bands, often measured in inches of water column. A failure in the relief system can lead to structural failure of the cover or implosion under vacuum conditions. Furthermore, the biogas environment is inherently hostile, characterized by high moisture, hydrogen sulfide (H2S), and siloxanes, which challenge the materials and moving parts of safety valves.
This article provides a neutral engineering analysis of the equipment offered by these two OEMs. By moving beyond brochure claims and focusing on mechanical design, leakage rates, maintenance accessibility, and API 2000 compliance, this guide aims to assist municipal consulting engineers and plant directors in making data-driven specification decisions for biogas handling systems. It sits within the wider field of digester manufacturers, where the gas train is typically bid as a separate package from the tank and mixing equipment.
Selecting the correct gas safety equipment requires a granular understanding of process variables. When comparing Varec Biogas (Ovivo) vs Shand & Jurs for Digestion, engineers must look past the brand name to the specific mechanical attributes that align with the facility’s risk profile and maintenance capabilities.
The primary driver for selection is the operating pressure relative to the maximum allowable working pressure (MAWP) of the digester tank or cover. Digesters typically operate at 6 to 12 inches w.c., with relief set points only marginally higher.
Biogas is wet and corrosive. The presence of H2S necessitates strict material controls. Standard aluminum construction is often sufficient for low-sulfide gas, but higher H2S requires upgrades.
The tightness of the valve as it approaches the set point defines its performance.
The most common failure mode for digester safety valves is sticking closed due to struvite crystallization, siloxane buildup, or freezing.
A specification that treats the PVRV as the digester’s sole overpressure protection has a gap in it, and the gap is usually on the emergency side.
Normal venting and emergency venting are different problems with different magnitudes. Normal venting handles gas production plus liquid displacement during pump-in, and for a municipal digester that is a modest flow that a correctly sized PVRV passes comfortably. Emergency venting — typically driven by external fire exposure under API 2000 — can require an order of magnitude more capacity. A PVRV sized for normal venting will not pass the emergency case, and adding overpressure to force it through will exceed the structural rating of a concrete cover long before the valve reaches full flow.
That is what the emergency relief manway is for. It is a large, low-set-pressure device, usually a weighted hatch, that opens and stays open. It is not redundancy for the PVRV; it is a separate device answering a separate question, and it must be in the design and in the hydraulic calculation. A plant with two PVRVs and no emergency vent has redundancy against one failure mode and no protection against the other.
Two downstream items complete the scheme and are routinely undersized. The flame arrester’s pressure drop at full flow subtracts directly from the available accumulation, so a valve set at 10″ w.c. on a cover rated for 12″ w.c. has 2″ of margin, and a flame arrester taking 3″ at rated flow has consumed all of it. Calculate the whole path, not the valve alone. And in pipe-away arrangements, condensate collecting in a low point adds static backpressure that raises the effective set pressure of the valve with no indication at the panel. Drip traps at every low point, drained on a schedule, are part of the safety system rather than a housekeeping detail.
The following tables provide a side-by-side analysis. Table 1 compares the manufacturers’ general approach to the digestion market. Table 2 provides a technical feature matrix for their pressure/vacuum relief valves, the most critical safety component. Model designations change; verify current series with the manufacturer before specifying.
| Manufacturer | Primary Strengths | Typical Applications | Limitations/Considerations | Maintenance Profile |
|---|---|---|---|---|
| Varec Biogas (Ovivo) | Large installed base and long-standing municipal standard; modular weight-loaded design; integrated system approach across covers and gas train; robust cast aluminum housings. | Municipal anaerobic digesters; waste gas burner systems; retrofits of existing Varec installations. | Weight-loaded pallet designs can stick if not cleaned regularly; seating performance depends on clean surfaces. | Moderate: Requires regular inspection for struvite and condensate. Parts are widely available but OEM parts carry a premium. |
| Shand & Jurs (L&J Technologies) | Diaphragm-assisted sealing technology offering tightness closer to set pressure; well-regarded insulation jacket design; resistance to seat freezing. | High-performance digesters; cold climate installations; applications requiring minimized gas loss. | Diaphragm materials must be carefully selected for chemical compatibility; slightly more complex internal mechanism than simple pallet weights. | Low to Moderate: Sealing design reduces simmer and fouling. Diaphragms are a wear item requiring replacement. |
| Feature | Varec Biogas (Typical) | Shand & Jurs (Typical) | Engineering Implication |
|---|---|---|---|
| Seating Technology | Weight-loaded pallet with O-ring or PTFE insert | Diaphragm-assisted seal energized by tank pressure | The diaphragm design typically allows operating pressure closer to set pressure without leakage. The pallet design is robust but may simmer earlier. |
| Winterization | Heat tracing and insulation jacket | All-weather construction plus insulation jackets | Both effective, but jacket fit and finish is critical. Thermal bridging at the flange is the usual weak point. |
| Material Options | Aluminum, 316SS, ductile iron | Aluminum, 316SS, cast iron, higher alloys | Both cover standard municipal needs. Broader alloy availability matters mainly for industrial crossover service. |
| Pallet Guides | Center stem / side guide | Center stem with low-friction polymer guides | Guide friction causes hysteresis. Both use low-friction sleeves to prevent sticking. |
| Maintenance Access | Removable hoods and covers | Quick-clamp access on some models | Ease of access encourages operator compliance. Bolted covers take longer to service than clamped designs. |
Drawing from commissioning reports and long-term operational logs, the following insights highlight practical considerations often missed in the initial specification of Varec Biogas (Ovivo) vs Shand & Jurs for Digestion systems.
The transition from construction to operation is where most errors in gas safety systems are discovered.
Operators must understand that these are not install-and-forget devices.
Proper sizing safeguards the physical assets. The methodology generally follows API 2000 / ISO 28300, tailored for low-pressure storage.
The required venting capacity is the sum of two components:
To ensure a robust procurement, the specification document must include:
The primary technical difference lies in the sealing technology. Shand & Jurs uses a diaphragm-assisted seal energized by tank pressure, creating a tighter seal closer to the set point. Varec typically uses a weight-loaded pallet with an O-ring or soft insert. The Varec design is simpler and robust; the Shand & Jurs design offers better leakage performance but introduces a diaphragm as a wear item.
Selection is based on API 2000 calculations. Calculate the required venting capacity for liquid pump-in and pump-out, thermal expansion and contraction, biological gas production, and emergency fire relief. Once the total is determined, select a valve size that can pass the normal-venting flow at a pressure typically no higher than 10-20% above the set pressure, and provide a separate emergency relief device for the fire case.
The most common causes are sticking due to struvite or frozen condensate, and corrosion. Biogas contains moisture and hydrogen sulfide; if the valve body is not heated or insulated in winter, ice forms. If the materials are not appropriate for sour service, H2S attacks them. Lack of seat cleaning leads to leakage or to the valve failing to open at set pressure.
With proper maintenance, the cast body housings of both manufacturers’ valves can last 20+ years. Internal soft goods (diaphragms, gaskets, O-rings) typically have a 3-5 year service life, and pallet assemblies may need refurbishment or replacement every 7-10 years depending on H2S exposure.
Yes, if the PVRV vents to atmosphere where an external ignition source could ignite the gas plume. The flame arrester prevents the flame front from travelling back into the digester. It adds pressure drop, which must be included in the accumulation calculation, and requires frequent cleaning to prevent clogging that would block the relief path.
Base pricing is broadly comparable for standard municipal specifications in the same size and material. Pricing moves with materials (aluminum versus stainless) and accessories (insulation jackets, position switches) more than with brand. Evaluate total cost of ownership based on maintenance frequency and the cost of replacement parts — diaphragms versus O-rings — rather than the quoted unit price.
They are separate scopes bid separately. The mixing technology choice is worked through in Varec Biogas (Ovivo) vs Smith & Loveless, the hydraulic-versus-gas-train interface in Smith & Loveless vs Shand & Jurs, and the wider supplier landscape in the review of digestion system OEMs.
The choice between Varec Biogas (Ovivo) vs Shand & Jurs for Digestion is rarely a matter of one being objectively better; it is a question of application fit. Varec (Ovivo) brings a large installed base and an integrated approach to the entire gas train, making it a standard choice for general municipal applications where simplicity is valued. Shand & Jurs distinguishes itself in applications demanding the highest sealing efficiency and freeze protection, often preferred in rigorous industrial environments or plants with strict emissions mandates.
For the specifying engineer, the priority must be accurate sizing across the whole relief path — valve, arrester, and emergency device — with density correction and clear material definitions. For the operator, success depends on rigorous adherence to inspection schedules. By understanding the mechanical nuances of these two suppliers, utilities can ensure the long-term safety and efficiency of their anaerobic digestion assets.